Industrial cooling circulating water system descaling and anti-scalingSaving water and reducing emissions to help achieve zero discharge

Popular search keywords: Como electronic scale removerDing ye remove scale and prevent scaleWaste heat recovery equipment scaling

Changes in a Zhangjiagang chemical new materials customer after using Como for two months

At the end of November 2018, we installed a Como water treatment system in the cooling circulating water system pump room of a chemical new materials company in Zhangjiagang. The purpose was to replace chemicals and improve water quality: the system not only had localized scaling issues but also more widespread corrosion problems (the incoming water was slightly acidic)。

(On-site installation diagram)

After using the chemical agent for just over a month, corrosion spots are already clearly visible on the hanging piece

After using the chemical agent for just over a month, corrosion spots are already clearly visible on the hanging piece.

After a few days of installation and use, Party A confirmed that the turbidity in the circulating water tank could be judged by the naked eye. In mid-December, the chemical company completed the final test, and then, except for retaining a small amount of alkali (as the incoming water was slightly acidic), all other chemicals were stopped. In the final water quality test, it was found that the total iron had significantly increased: from around 1mg/l previously to over 4mg/l。This is the result of the rust being stripped away along with the scale during the Como signal descaling process. As the scale is completely removed, the total iron content will gradually decrease. This was confirmed in subsequent weekly water sample tests。

Zhangjiagang XXXX Chemical New Materials Water Quality Test Results

NO.

Test Subject

Unit

18-12-25号

19-01-02号

19-01-09号

19-01-16号

Remarks

1

Total hardness

mg/l

145

120

90

115


2

specific conductance

μs/cm

1600

1600

1700

1300


3

total alkalinity

mg/l

25

45

90

105


4

SO42-

mg/l

29

-

-

-


5

Cl-

mg/l

19.5

-

-

-


6

total iron

mg/l

0.86

0.17

0.15

0.06


Summaries: From the four water quality tests, the corrosion problem of the system has been significantly suppressed. At the same time, it can be judged that a small amount of old scale has also been basically removed cleanly。


Attachment 1: Two Routine Tests by Chemical Pharmaceuticals, Inc

routine test

Date

pH

conductivityμs/cm

turbidity, mg/L

calcium hardness mg/L

total hardnessmg/L

total alkalinitymg/L

chloride ion mg/L

Fe,mg/L

chemical concentration,mg/L

12月14日

7.2

286

1.6

119.15

324.08

21.33

53.38

4.58

125

Attachment 2: On-site water tank corrosion and the effect of the new hanging piece for 2 months

Water tank corrosion

Water tank corrosion

The effect of 2 months of new hangings